EWADH12TZXSC2 | EWADH16TZXSC2 | EWADC14TZXSC2 | EWADC11TZXSC2 | EWADC12TZXSC2 | EWADC15TZXSC2 | EWADH17TZXSC2 | ||||
---|---|---|---|---|---|---|---|---|---|---|
Cooling capacity | Nom. | kW | 1,280 | 1,667 | 1,399 | 1,124 | 1,206 | 1,539 | 1,780 | |
Capacity control | Method | Variable | Variable | Variable | Variable | Variable | Variable | Variable | ||
Minimum capacity | % | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | 12.5 | ||
Power input | Cooling | Nom. | kW | 401.6 | 524.7 | 431.7 | 354 | 375.9 | 478.8 | 575.4 |
EER | 3.19 | 3.18 | 3.24 | 3.17 | 3.21 | 3.22 | 3.09 | |||
Dimensions | Unit | Depth | Mm | 12,302 | 13,202 | 11,402 | 10,510 | 11,402 | 12,302 | 14,104 |
Height | Mm | 2,540 | 2,540 | 2,540 | 2,540 | 2,540 | 2,540 | 2,540 | ||
Width | Mm | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | 2,282 | ||
Weight | Operation weight | kg | 11,526 | 12,575 | 11,727 | 9,879 | 11,123 | 12,145 | 13,048 | |
Unit | kg | 10,515 | 11,564 | 10,716 | 9,322 | 10,112 | 11,134 | 12,037 | ||
Water heat exchanger | Type | Shell and tube | Shell and tube | Shell and tube | Shell and tube | Shell and tube | Shell and tube | Shell and tube | ||
Water volume | l | 1,011 | 1,011 | 1,011 | 557 | 1,011 | 1,011 | 1,011 | ||
Air heat exchanger | Type | Microchannel | Microchannel | Microchannel | Microchannel | Microchannel | Microchannel | Microchannel | ||
Fan | Air flow rate | Nom. | l/s | 99,151 | 142,876 | 122,464 | 83,897 | 91,524 | 132,670 | 153,081 |
Speed | rpm | 700 | 900 | 900 | 700 | 700 | 900 | 900 | ||
Compressor | Quantity | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||
Type | Inverter driven single screw compressor | Inverter driven single screw compressor | Inverter driven single screw compressor | Inverter driven single screw compressor | Inverter driven single screw compressor | Inverter driven single screw compressor | Inverter driven single screw compressor | |||
Sound power level | Cooling | Nom. | dBA | 97 | 102 | 101 | 95 | 96 | 101 | 102 |
Sound pressure level | Cooling | Nom. | dBA | 74 | 79 | 78 | 73 | 73 | 78 | 79 |
Refrigerant | Type | R-134a | R-134a | R-134a | R-134a | R-134a | R-134a | R-134a | ||
GWP | 1,430 | 1,430 | 1,430 | 1,430 | 1,430 | 1,430 | 1,430 | |||
Circuits | Quantity | 2 | 2 | 2 | 2 | 2 | 2 | 2 | ||
Charge | kg | 220 | 250 | 200 | 175 | 200 | 220 | 270 | ||
Power supply | Phase | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | 3~ | ||
Frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 | 50 | ||
Voltage | V | 400 | 400 | 400 | 400 | 400 | 400 | 400 | ||
Compressor | Starting method | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven | VFD driven |