Specifications Table for FCAG-B / AZAS-MY1

FCAG125BVEB / AZAS125M7Y1B FCAG140BVEB / AZAS140M7Y1B
Cooling capacity Nom. kW 12.1 (1) 13.4 (1)
Heating capacity Nom. kW 13.5 (2) 15.5 (2)
Space cooling Capacity Pdesign kW 12.1 13.0
  SEER   5.40 6.00
  Annual energy consumption kWh/a 1,345 1,300
Space heating (Average climate) Capacity Pdesign kW 6.00 7.80
  SCOP/A   3.80 4.31
  Annual energy consumption kWh/a 2,211 2,534
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - See separate drawing for operation range (3) - See separate drawing for operation range
  (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data