Specifications Table for FCQG-F / AZQS-BY1 UK

FCQG100FVEB / AZQS100B7Y1B UK FCQG125FVEB / AZQS125B7Y1B UK FCQG140FVEB / AZQS140B7Y1B UK
Cooling capacity Nom. kW 9.5 12.1 13.0
Space cooling SEER   5.50
  Annual energy consumption kWh/a 605
  Capacity Pdesign kW 9.50
  Energy efficiency class   A
Space heating (Average climate) Capacity Pdesign kW 7.60
  SCOP/A   3.85
  Energy efficiency class   A
  Annual energy consumption kWh/a 2,764
Nominal efficiency EER   3.21 3.10 2.81
  Annual energy consumption kWh 1,480 1,952 2,313
  COP   3.50 3.41 3.30
  Energy labeling Directive Cooling   A B
    Heating   B B
Heating capacity Nom. kW 10.8 13.5 15.5
Notes (1) - Annual energy consumption is according to Energy labeling directive 2002/31/EC (1) - Annual energy consumption is according to Energy labeling directive 2002/31/EC (1) - Annual energy consumption is according to Energy labeling directive 2002/31/EC
  (2) - SEER and SCOP are according to EN 14825 (2) - SEER and SCOP are according to EN 14825 (2) - SEER and SCOP are according to EN 14825
  (3) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (3) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (3) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load