Specifications Table for FWC-BF

FWC06B5FV1B FWC07B5FV1B FWC08B5FV1B FWC09B5FV1B
Sound pressure level Low dBA 21.0 22.0 24.0 28.0
  High dBA 29.0 33.0 39.0 43.0
Standard Accessories Installation and operation manual 1 1 1 1
  Installation guide 1 1 1 1
  Drain hose 1 1 1 1
  Metal clamp for drain hose 1 1 1 1
  Washer for hanger bracket 8 8 8 8
  Screws 4 4 4 4
  O ring 4 4 4 4
  Insulation 6 6 6 6
Total sound power level Low dBA 33.0 36.0 36.0 40.0
  High dBA 43.0 47.0 53.0 57.0
Water flow Water pressure drop Heating High kPa 18 22 30 38
    Cooling High kPa 15 18 23 30
Piping connections Drain OD mm VP25 (External dia.32, internal dia. 25) VP25 (External dia.32, internal dia. 25) VP25 (External dia.32, internal dia. 25) VP25 (External dia.32, internal dia. 25)
  Water Inlet   3/4" BSP (female thread) 3/4" BSP (female thread) 3/4" BSP (female thread) 3/4" BSP (female thread)
    Outlet   3/4" BSP (female thread) 3/4" BSP (female thread) 3/4" BSP (female thread) 3/4" BSP (female thread)
Power input High kW 0.046 0.055 0.077 0.107
  Low kW 0.035 0.038 0.040 0.046
Allowed water temperature Heating Max. °C 70 (4) 70 (4) 70 (4) 70 (4)
    Min. °C 5 (4) 5 (4) 5 (4) 5 (4)
  Cooling Min. °C 5 (4) 5 (4) 5 (4) 5 (4)
    Max. °C 70 (4) 70 (4) 70 (4) 70 (4)
Dimensions Unit Width mm 840 840 840 840
    Depth mm 840 840 840 840
    Height mm 288 288 288 288
Weight Unit kg 29 29 29 29
Fan Air flow rate Low m³/h 708 804 852 1,014
    High m³/h 1,032 1,200 1,476 1,746
Cooling capacity (standard conditions) Total capacity 4-pipe Low kW 4.3 (1) 4.6 (1) 4.8 (1) 5.7 (1)
    High kW 5.9 (1) 6.3 (1) 7.2 (1) 8.3 (1)
  Sensible capacity 4-pipe Low kW 3.1 (1) 3.3 (1) 3.5 (1) 4.0 (1)
    High kW 4.2 (1) 4.6 (1) 5.4 (1) 6.4 (1)
Heating capacity (standard conditions) Capacity 4-pipe Low kW 5.2 (3) 5.5 (3) 5.8 (3) 6.8 (3)
    High kW 6.9 (3) 7.8 (3) 9.2 (3) 10.4 (3)
Power supply Phase   1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240
Notes (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C (1) - Cooling: air 27°CDB, 19°CWB; entering water 7°C; leaving water 12°C
  (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C (2) - Heating: 2 pipe: air 20°CDB, 15°CWB; entering water 45°C; leaving water 40°C
  (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C (3) - Heating: 4 pipe: air 20°CDB, 15°CWB; entering water 65°C; leaving water 55°C
  (4) - Do not let water of less than 5°C or more than 50°/70°C enter the unit, this may damage the unit (4) - Do not let water of less than 5°C or more than 50°/70°C enter the unit, this may damage the unit (4) - Do not let water of less than 5°C or more than 50°/70°C enter the unit, this may damage the unit (4) - Do not let water of less than 5°C or more than 50°/70°C enter the unit, this may damage the unit