Specifications Table for FXFN-B

FXFN40B2VEB FXFN50B2VEB FXFN63B2VEB FXFN80B2VEB
Cooling capacity Total capacity At high fan speed kW 4.5 5.6 7.1 9.0
Heating capacity Total capacity At high fan speed kW 5.0 6.3 8.0 10.0
Power input - 50Hz Cooling At high fan speed kW 0.019 0.036 0.067 0.118
  Heating At high fan speed kW 0.019 0.036 0.067 0.118
Dimensions Unit Height mm 246 246 246 288
    Width mm 840 840 840 840
    Depth mm 840 840 840 840
Weight Unit kg 26 26 26 29
Casing Colour   Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised)
  Material   Galvanized steel plate Galvanized steel plate Galvanized steel plate Galvanized steel plate
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 15.5 21.0 26.8 35.5
      At low fan speed m³/min 11.5 15.0 18.0 23.5
Refrigerant Type   R-744 R-744 R-744 R-744
  GWP   1.0 1.0 1.0 1.0
Sound power level Cooling At high fan speed dBA 53.0 57.0 62.0 66.0
Sound pressure level Cooling At high fan speed dBA 35.0 39.0 44.0 48.0
    At medium fan speed dBA 33.0 37.0 42.0 46.0
    At low fan speed dBA 31.0 35.0 40.0 44.0
  Heating At high fan speed dBA 36.0 40.0 45.0 49.0
    At medium fan speed dBA 34.0 38.0 43.0 47.0
    At low fan speed dBA 32.0 36.0 41.0 45.0
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 9.52 9.52
  Gas Type   Braze connection Braze connection Braze connection Braze connection
    OD mm 12.7 12.7 12.7 12.7
  Drain   VP25 (I.D. 32/O.D. 25) VP25 (I.D. 32/O.D. 25) VP25 (I.D. 32/O.D. 25) VP25 (I.D. 32/O.D. 25)
Decoration panel Model   BYCQ140E2W1/BYCQ140E2W1W/BYCQ140E2W1B BYCQ140E2W1/BYCQ140E2W1W/BYCQ140E2W1B BYCQ140E2W1/BYCQ140E2W1W/BYCQ140E2W1B BYCQ140E2W1/BYCQ140E2W1W/BYCQ140E2W1B
  Dimensions Height mm 65 65 65 65
    Width mm 950 950 950 950
    Depth mm 950 950 950 950
  Weight kg 5.5 5.5 5.5 5.5
Decoration panel 2 Model   BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B BYCQ140E2GFW1, BYCQ140E2GFW1B
  Dimensions Height mm 148 148 148 148
    Width mm 950 950 950 950
    Depth mm 950 950 950 950
  Weight kg 10.3 10.3 10.3 10.3
Decoration panel 3 Model   BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB BYCQ140E2P, BYCQ140E2PB
  Dimensions Height mm 106 106 106 106
    Width mm 950 950 950 950
    Depth mm 950 950 950 950
  Weight kg 6.5 6.5 6.5 6.5
Air filter Type   Resin net Resin net Resin net Resin net
Standard Accessories Washer for hanger bracket 8 8 8 8
  Wire clamp material 7 7 7 7
  Clamp for drain hose 1 1 1 1
  Clamps 1 1 1 1
  Drain hose 1 1 1 1
  Installation and operation manual 1 1 1 1
  Installation guide 1 1 1 1
  Insulation for fitting 2 2 2 2
  Screws 4 4 4 4
  Sealing pad 1 1 1 1
Power supply Name   VE VE VE VE
  Phase   1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6 6 6 6
Notes (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting.
  (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
  (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB
  (4) - The sound power level is an absolute value indicating the power which a sound source generates. (4) - The sound power level is an absolute value indicating the power which a sound source generates. (4) - The sound power level is an absolute value indicating the power which a sound source generates. (4) - The sound power level is an absolute value indicating the power which a sound source generates.
  (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%.
  (7) - MCA/MFA: MCA = 1.1 x FLA (7) - MCA/MFA: MCA = 1.1 x FLA (7) - MCA/MFA: MCA = 1.1 x FLA (7) - MCA/MFA: MCA = 1.1 x FLA
  (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker (8) - Instead of a fuse, use a circuit breaker
  (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA
  (10) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers. (10) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers. (10) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers. (10) - BYCQ140E2W1: pure white standard panel with grey louvers; BYCQ140E2W1W: pure white standard panel with white louvers; BYCQ140E2W1B: black standard panel with black louvers.
  (11) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt. (11) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt. (11) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt. (11) - The BYCQ140E2W1W has white insulations. Be informed that formation of dirt on white insulation is visibly stronger and that it is consequently not advised to install the BYCQ140E2W1W decoration panel in enviroments exposed to concentrations of dirt.
  (12) - Contains fluorinated greenhouse gases (12) - Contains fluorinated greenhouse gases (12) - Contains fluorinated greenhouse gases (12) - Contains fluorinated greenhouse gases