Specifications Table for FXMQ-PAVE

FXMQ140PAVE
Sound pressure level Cooling At low fan speed dBA 43.0
    Super high dBA 46.0
Standard Accessories Operation manual Operation manual
  Installation manual Installation manual
  Drain hose Drain hose
  Sealing pads Sealing pads
  Clamps Clamps
  Washer Washer
  Screws Screws
  Insulation for fitting Insulation for fitting
  Clamp metal Clamp metal
  Air discharge flange Air discharge flange
  Air suction flange Air suction flange
System Connectable outdoor unit system   R410A VRV Series
Power input - 50Hz Cooling At high fan speed kW 0.461
  Heating At high fan speed kW 0.449
Cooling capacity Total capacity At high fan speed kW 16.0 (1)
Piping connections Liquid OD mm 9.5
    Type   Flare connection
  Gas OD mm 15.9
    Type   Flare connection
  Drain   VP25 (O.D. 32 / I.D. 25)
Sound power level Cooling At high fan speed dBA 45.0
Dimensions Unit Width mm 1,400
    Depth mm 700
    Height mm 300
Casing Material   Galvanised steel plate
Weight Unit kg 46
Fan External static pressure - 50Hz High Pa 140
    Low Pa 50
  External static pressure - 60Hz High Pa 140
    Low Pa 50
  Air flow rate - 50Hz Cooling At high fan speed m³/min 39
      At low fan speed m³/min 32
      Super high m³/min 46
  Air flow rate - 60Hz Cooling High m³/min 39
      Super high m³/min 46
      Low m³/min 32
Heating capacity Total capacity At high fan speed kW 18.0 (2)
Current - 50Hz Maximum fuse amps (MFA) A 16
Power supply Phase   1~
  Name   VE
  Frequency Hz 50/60
  Voltage V 220-240/220
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - External static pressure is changeable in 7 stages (20, 25, 32 class); 13 stages (40 class); 14 stages (50, 63, 80, 100, 125 class); 10 stages (140 class) within the range of the remote control.
  (5) - Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% and more.