Specifications Table for FXSN-B

FXSN40B2VEB FXSN50B2VEB FXSN63B2VEB FXSN80B2VEB
Cooling capacity Total capacity At high fan speed kW 4.50 5.60 7.10 9.00
Heating capacity Total capacity At high fan speed kW 5.0 6.3 8.0 10.0
Power input - 50Hz Cooling At high fan speed kW 0.128 0.165 0.148 0.279
  Heating At high fan speed kW 0.128 0.179 0.160 0.313
Dimensions Unit Height mm 245 245 245 245
    Width mm 1000 1000 1400 1400
    Depth mm 800 800 800 800
Weight Unit kg 40 40 50 50
Casing Colour   Not painted (galvanised) Not painted (galvanised) Not painted (galvanised) Not painted (galvanised)
  Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Required ceiling void > mm 300 300 300 300
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 23.0 25.0 29.4 37.6
      At low fan speed m³/min 16.0 17.0 21.1 26.9
  External static pressure - 50Hz High Pa 120 120 120 120
  External static pressure - 60Hz High Pa 120 120 120 120
Refrigerant Type   R-744 R-744 R-744 R-744
  GWP   1.0 1.0 1.0 1.0
Sound power level Cooling At high fan speed dBA 61.0 63.0 61.0 66.0
Sound pressure level Cooling At high fan speed dBA 39.0 41.0 39.0 44.0
    At medium fan speed dBA 36.5 38.5 36.5 41.5
    At low fan speed dBA 34.0 36.0 34.0 39.0
  Heating At high fan speed dBA 41.0 44.0 44.0 48.0
    At medium fan speed dBA 38.5 41.5 41.5 45.0
    At low fan speed dBA 36.0 39.0 39.0 42.0
Piping connections Liquid Type   Braze connection Braze connection Braze connection Braze connection
    OD mm 9.52 9.52 9.52 9.52
  Gas Type   Braze connection Braze connection Braze connection Braze connection
    OD mm 12.7 12.7 12.7 12.7
  Drain   VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm VP20 (I.D. 20/O.D. 26), drain height 625 mm
Air filter Type   Resin net Resin net Resin net Resin net
Standard Accessories Washer for hanger bracket 1 1 1 1
  Clamps 4 4 4 4
  Drain hose 1 1 1 1
  Installation and operation manual 1 1 1 1
  Insulation for fitting 2 2 2 2
  Metal clamp for drain hose 1 1 1 1
  Screws 40 40 40 40
  Sealing pad 5 5 5 5
Power supply Name   VE VE VE VE
  Phase   1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6 6 6 6
Notes (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting. (1) - Values are valid for the factory setting.
  (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
  (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
  (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual)
  (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%. (7) - Maximum allowable voltage range variation between phases is 2%.
  (8) - MCA/MFA: MCA = 1.1 x FLA (8) - MCA/MFA: MCA = 1.1 x FLA (8) - MCA/MFA: MCA = 1.1 x FLA (8) - MCA/MFA: MCA = 1.1 x FLA
  (9) - Instead of a fuse, use a circuit breaker (9) - Instead of a fuse, use a circuit breaker (9) - Instead of a fuse, use a circuit breaker (9) - Instead of a fuse, use a circuit breaker
  (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA
  (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases