| FXSN40B2VEB | FXSN50B2VEB | FXSN63B2VEB | FXSN80B2VEB | |||||
|---|---|---|---|---|---|---|---|---|
| Cooling capacity | Total capacity | At high fan speed | kW | 4.50 | 5.60 | 7.10 | 9.00 | |
| Heating capacity | Total capacity | At high fan speed | kW | 5.0 | 6.3 | 8.0 | 10.0 | |
| Power input - 50Hz | Cooling | At high fan speed | kW | 0.128 | 0.165 | 0.148 | 0.279 | |
| Heating | At high fan speed | kW | 0.128 | 0.179 | 0.160 | 0.313 | ||
| Dimensions | Unit | Height | mm | 245 | 245 | 245 | 245 | |
| Width | mm | 1000 | 1000 | 1400 | 1400 | |||
| Depth | mm | 800 | 800 | 800 | 800 | |||
| Weight | Unit | kg | 40 | 40 | 50 | 50 | ||
| Casing | Colour | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | Not painted (galvanised) | |||
| Material | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | Galvanised steel plate | ||||
| Required ceiling void > | mm | 300 | 300 | 300 | 300 | |||
| Fan | Air flow rate - 50Hz | Cooling | At high fan speed | m³/min | 23.0 | 25.0 | 29.4 | 37.6 |
| At low fan speed | m³/min | 16.0 | 17.0 | 21.1 | 26.9 | |||
| External static pressure - 50Hz | High | Pa | 120 | 120 | 120 | 120 | ||
| External static pressure - 60Hz | High | Pa | 120 | 120 | 120 | 120 | ||
| Refrigerant | Type | R-744 | R-744 | R-744 | R-744 | |||
| GWP | 1.0 | 1.0 | 1.0 | 1.0 | ||||
| Sound power level | Cooling | At high fan speed | dBA | 61.0 | 63.0 | 61.0 | 66.0 | |
| Sound pressure level | Cooling | At high fan speed | dBA | 39.0 | 41.0 | 39.0 | 44.0 | |
| At medium fan speed | dBA | 36.5 | 38.5 | 36.5 | 41.5 | |||
| At low fan speed | dBA | 34.0 | 36.0 | 34.0 | 39.0 | |||
| Heating | At high fan speed | dBA | 41.0 | 44.0 | 44.0 | 48.0 | ||
| At medium fan speed | dBA | 38.5 | 41.5 | 41.5 | 45.0 | |||
| At low fan speed | dBA | 36.0 | 39.0 | 39.0 | 42.0 | |||
| Piping connections | Liquid | Type | Braze connection | Braze connection | Braze connection | Braze connection | ||
| OD | mm | 9.52 | 9.52 | 9.52 | 9.52 | |||
| Gas | Type | Braze connection | Braze connection | Braze connection | Braze connection | |||
| OD | mm | 12.7 | 12.7 | 12.7 | 12.7 | |||
| Drain | VP20 (I.D. 20/O.D. 26), drain height 625 mm | VP20 (I.D. 20/O.D. 26), drain height 625 mm | VP20 (I.D. 20/O.D. 26), drain height 625 mm | VP20 (I.D. 20/O.D. 26), drain height 625 mm | ||||
| Air filter | Type | Resin net | Resin net | Resin net | Resin net | |||
| Standard Accessories | Washer for hanger bracket | 1 | 1 | 1 | 1 | |||
| Clamps | 4 | 4 | 4 | 4 | ||||
| Drain hose | 1 | 1 | 1 | 1 | ||||
| Installation and operation manual | 1 | 1 | 1 | 1 | ||||
| Insulation for fitting | 2 | 2 | 2 | 2 | ||||
| Metal clamp for drain hose | 1 | 1 | 1 | 1 | ||||
| Screws | 40 | 40 | 40 | 40 | ||||
| Sealing pad | 5 | 5 | 5 | 5 | ||||
| Power supply | Name | VE | VE | VE | VE | |||
| Phase | 1~ | 1~ | 1~ | 1~ | ||||
| Frequency | Hz | 50/60 | 50/60 | 50/60 | 50/60 | |||
| Voltage | V | 220-240/220 | 220-240/220 | 220-240/220 | 220-240/220 | |||
| Current - 50Hz | Maximum fuse amps (MFA) | A | 6 | 6 | 6 | 6 | ||
| Notes | (1) - Values are valid for the factory setting. | (1) - Values are valid for the factory setting. | (1) - Values are valid for the factory setting. | (1) - Values are valid for the factory setting. | ||||
| (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | (2) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m | |||||
| (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | (3) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m | |||||
| (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | (4) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. | |||||
| (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) | (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) | (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) | (5) - External static pressure is changeable to set by the remote control (from standard to high, see installation manual) | |||||
| (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | (6) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. | |||||
| (7) - Maximum allowable voltage range variation between phases is 2%. | (7) - Maximum allowable voltage range variation between phases is 2%. | (7) - Maximum allowable voltage range variation between phases is 2%. | (7) - Maximum allowable voltage range variation between phases is 2%. | |||||
| (8) - MCA/MFA: MCA = 1.1 x FLA | (8) - MCA/MFA: MCA = 1.1 x FLA | (8) - MCA/MFA: MCA = 1.1 x FLA | (8) - MCA/MFA: MCA = 1.1 x FLA | |||||
| (9) - Instead of a fuse, use a circuit breaker | (9) - Instead of a fuse, use a circuit breaker | (9) - Instead of a fuse, use a circuit breaker | (9) - Instead of a fuse, use a circuit breaker | |||||
| (10) - Select wire size based on the value of MCA | (10) - Select wire size based on the value of MCA | (10) - Select wire size based on the value of MCA | (10) - Select wire size based on the value of MCA | |||||
| (11) - Contains fluorinated greenhouse gases | (11) - Contains fluorinated greenhouse gases | (11) - Contains fluorinated greenhouse gases | (11) - Contains fluorinated greenhouse gases | |||||