Specifications Table for FXUA-A

FXUA50AVEB FXUA71AVEB FXUA100AVEB FXUA50AVMB (Archived) (Preliminary) FXUA71AVMB (Archived) (Preliminary) FXUA100AVMB (Archived) (Preliminary)
Sound pressure level Heating At high fan speed dBA       37 40.0 47.0
    At low fan speed dBA       33 36.0 40.0
    At medium fan speed dBA       35 38.0 44.0
  Cooling At low fan speed dBA       33 36.0 40.0
    At high fan speed dBA       37 40.0 47.0
    At medium fan speed dBA       35 38.0 44.0
Refrigerant GWP         675 675 675
  Type         R-32 R-32 R-32
Power input - 50Hz Cooling At high fan speed kW       0.050 0.090 0.200
Cooling capacity Total capacity At high fan speed kW       5.6 8.0 11.2
Piping connections Liquid OD mm       6.35 6.35 9.52
  Gas OD mm       12.7 12.7 12.9
  Drain         I.D. 20/O.D. 26 I.D. 20/O.D. 26 I.D. 20/O.D. 26
Sound power level Cooling At high fan speed dBA       55 58 65
Air filter Type         Resin net with mold resistance Resin net with mold resistance Resin net with mold resistance
Dimensions Unit Width mm       950 950 950
    Depth mm       950 950 950
    Height mm       198 198 198
Casing Material         Resin Resin Resin
Weight Unit kg       26 26 27
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min       17 22.5 31.0
      At low fan speed m³/min       13 16.0 21.0
Heating capacity Total capacity At high fan speed kW       6.3 9.0 12.5
Current - 50Hz Maximum fuse amps (MFA) A       16 16 16
Power supply Phase         1~ 1~ 1~
  Frequency Hz       50/60 50/60 50/60
  Voltage V       220-240/220-230 220-240/220-230 220-240/220-230
Notes       (1) - Contains fluorinated greenhouse gases (1) - Contains fluorinated greenhouse gases (1) - Contains fluorinated greenhouse gases
Cooling capacity Total capacity At high fan speed kW 5.6 8.0 11.2
Heating capacity Total capacity At high fan speed kW 6.3 9.0 12.5
Power input - 50Hz Cooling At high fan speed kW 0.029 0.055 0.117
  Heating At high fan speed kW 0.029 0.055 0.117
Dimensions Unit Height mm 198 198 198
    Width mm 950 950 950
    Depth mm 950 950 950
Weight Unit kg 27 27 28
Casing Colour   Fresh White Fresh White Fresh White
  Material   Resin Resin Resin
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 17.0 22.5 31.0
      At low fan speed m³/min 13.0 16.0 21.0
Refrigerant Type   R-32 R-32 R-32
  GWP   675 675 675
Sound power level Cooling At high fan speed dBA 55.0 58.0 65.0
Sound pressure level Cooling At high fan speed dBA 37.0 40.0 47.0
    At medium fan speed dBA 35.0 38.0 44.0
    At low fan speed dBA 33.0 36.0 40.0
  Heating At high fan speed dBA 37.0 40.0 47.0
    At medium fan speed dBA 35.0 38.0 44.0
    At low fan speed dBA 33.0 36.0 40.0
Piping connections Liquid Type   Flare connection Flare connection Flare connection
    OD mm 6.4 6.4 9.5
  Gas Type   Flare connection Flare connection Flare connection
    OD mm 12.7 12.7 15.9
  Drain   VP20 VP20 VP20
Air filter Type   Resin net Resin net Resin net
Standard Accessories Thermal insulation tube 3 3 3
  Non woven fabric 1 1 1
  Drain joint 1 1 1
  Hose band 1 1 1
  Wire clamp material 10 10 10
  Drain hose 1 1 1
  Extension auxiliary pipe 1 1 1
  Screws 5 5 5
  Sealing material 4 4 4
  Washer 8 8 8
  Washer fixing plate 1 1 1
Power supply Phase   1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 6 6 6
Notes (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
  (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates. (3) - The sound power level is an absolute value indicating the power which a sound source generates.
  (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker (4) - Instead of a fuse, use a circuit breaker
  (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA (5) - Select wire size based on the value of MCA
  (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases (6) - Contains fluorinated greenhouse gases